IDENTIFICATION AND VERIFICATION OF HIERARCHY OF DFIG CONVERTER CONTROLS FOR POWER SYSTEM DAMPING

Abu H.M.A. Rahim, Ibrahim O. Habiballah, and Edwin P. Nowicki

Keywords

Wind power generation, doubly fed induction generator, renewableenergy, converter controls, POD controllerNomenclaturePm turbine power outputVw wind speedβ blade pitch angleλ tip speed ratiod-q direct and quadrature axesRs, xs DFIG stator resistance and reactanceRr, xr DFIG rotor resistance and reactancexm DFIG stator-rotor mutual reactance∗ Department of Electrical Engineering, K.F. Universityof Petroleum and Minerals, Dhahran, Saudi Arabia;e-mail: {ibrahimh, ahrahim}@

Abstract

This article employs two decomposition techniques and the residue principles to determine the order of the converter controls of a doubly fed induction generator (DFIG) in terms of providing system damping. The dynamic model of the various components of the DFIG system – the wind turbine, induction generator, converter system, the load and transmission network are derived and 4 converter controls identified. The hierarchy analysis demonstrates that out of 4 converter controls the magnitude of the rotor applied voltage is the most effective one. The finding was verified by simulating the system through both lead-lag as well as proportional- integral (PI) controller designs, the controller parameters being found through the residue principle. Simulation studies on the doubly fed generator system show that both the controller designs provide good damping to the system, the PI control being slightly superior. The controlled rotor voltage was observed to be able to avert voltage collapse in the system arising in the event of severe disturbance conditions.

Important Links:



Go Back